2016/3/1??????view:

Power transformer operation such as the occurrence of localized heating, in many cases, did not perform as electrical anomalies, and first exhibited is abnormal oil and gas decomposition. Namely, the oil in local high temperature decomposition for gas gathering in the transformer cover at the upper end and the gas relay. The difference between gas production and gas production rate; the size, is actually the difference between the size of the overheating fault.

Ⅰ 、after the action of the light gas. Signal light gas action, first of all, we should stop the audio signal, and check the gas relay gas, to ascertain the reasons.
1, non fault. Such as: air intrusion transformer, filter oil; oil level is reduced to below the gas relay (float type gas relay) or level decreases sharply (flapper gas relay); gas protection secondary circuit fault (such as inlet gas relay junction box, terminal row or secondary cable short circuit). As for the external reasons to determine the cause of action, the recovery signal, the transformer can continue to run.
2, reasons, main transformer fault. If you are not sure is due to external reasons caused by gas signal action, and found no other abnormalities should be gas protection tripping circuit input, at the same time, strengthen the monitoring of transformer, carefully observe the development and changes.

Ⅱ、heavy gas protection action: after the operation of the transformer gas protection tripping signal, or the gas and gas trip at the same time, first consider the transformer internal fault may. Treatment of this kind of transformer should be very careful.
The gas generated in the transformer fault is due to the nature of transformer in different parts of ascertain gas relay gas, gas concentration, the speed and quantity degree is crucial. Due to different forms of overheating. Therefore, to determine the nature and extent of the transformer fault is crucial.

1, of agglomeration, and the gas is colored non smelly and nonflammable, gas action is caused by the oil separated from the air, then you can decide as belonging to the non fault, power transformer can continue to run.

2,  the gas is flammable, it is most likely due to the internal fault of transformer. For this type of transformer, without inspection and test before, are not allowed to put into operation.

Power transformer protection action of gas as a precursor of internal accident, or is itself an internal accident. Therefore, on this kind of transformer send, send, supervision of operation should be especially careful, the cause of the accident did not check Mingqian shall not send.

主站蜘蛛池模板: 中文日本在线| 丁香五月一区韩日av成人免费在线观看七月丁香天天肏天天 | 无码一区在线影院| 麻豆一姐视传媒短视频在线观看| 国产亚洲精品A在线无码| 成人无码电影| 亚洲精品无码视频在线观看| 欧美精品九九99久久在免费线 | 精品久久综合一区二区| 国产v最新精品自在自线| 成人免费视频无码专区| 亚洲欧美日韩中文字幕在线一| 亚洲免费永久精品| 国产91司机在线观看| 精品亚洲大全| 五月情视频在线观看| 美女把小内内脱个精光的照片| 国产熟女视频| a级国产电影在线观看| 天天综合天堂在线视频| 久久久久久久久精品| 国产精品第3页| 中文字幕精品1在线| 欧亚成人A片一区二区| 鲁鲁夜夜天天综合视频| 国产精品永久免费视频精品久| 91在线亚洲| 日本最新中文字幕| 激情五月婷婷色| 成品大香煮伊在2024一区| 午夜国产在线精品一区二区| 久久久久一级片| 国产成人狂喷潮在线观看2345| 一级免费毛片| 色网站视频| 精品一区二区三区自拍| 懂色aⅴ一区二区三区免费| 91精品一区| 波多野结衣潮喷系列| 亚洲国产av无码精品无广告| 久久综合精品国产丝袜长腿|